Liquid Level Relay Dual Probe Pump Down 4.7K-100K Ohms Sensitivity

Features

  • Family: LCP
  • Function/Output: Dual Probe Pump Down (w/ Pin Configuration = Crouzet & Symcom unit)
  • Input Voltage: 120VAC
  • Sensitivity Range: 4.7K – 100K ohms
  • Function: DUAL PROBE PUMP DOWN
  • Function Name: LCP2D
  • Timing: Sensitivity Range: 4.7K - 100K Ohms
  • Input: 120V AC
  • Output: 10A SPDT
  • Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
  • Insulation Voltage: 2,000 volts
  • Probe Voltage: 5V DC Pulsed
  • Load Burden: 2 VA
  • Output Contacts: 10A @ 240V AC/7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
  • Life: Mechanical: 10000000 operations; Full Load: 100000 operations
  • Temperature: -28° to 65°C (-18° to 149°F)
  • Response Times: Pick-up: 1 second; Drop-out: 1 second

Overview

Pump Down (Drain): When the liquid level rises and touches the probe, a xed time delay begins and the LED ashes Red. This time delay prevents rapid cycling of the output relay and its load. At the end of the time delay, the output relay energizes, and the LED is Red ON. The pump is ON to drain the tank. The relay remains energized until the liquid level falls below the probe level. The output relay de-energizes, turning off the pump, and remains de-energized and the LED is Green ON until the liquid level rises and touches the probe.

,